Off-grid battery bank calculator
Work out how much storage an independent home needs, how to arrange the batteries, what the inverter must deliver and how much solar it takes to refill the bank after a cloudy spell.
Size the bank
1. Energy and autonomy
2. Bank layout
3. Inverter
4. Recharging with solar
The defaults reproduce the worked example in our off-grid solar guide: a home using 3 kWh a day, carried for two days by a lithium bank. Replace them with your own figures. The results are first-pass planning numbers to compare against a designer’s proposal, not an equipment specification.
The formulas behind each number
Nominal storage (Wh) = daily energy × days of autonomy ÷ (usable share × inverter efficiency × cold-weather capacity). With the defaults: 3,000 × 2 ÷ (0.80 × 0.90 × 1.00) = 8,333 Wh. Amp-hours are the same figure divided by system voltage: 8,333 ÷ 48 ≈ 174 Ah.
Battery layout. Batteries in series add voltage, so the number in each string is the system voltage divided by one battery’s voltage. Strings in parallel add amp-hours, so the number of strings is the required amp-hours divided by one battery’s amp-hours, rounded up. Two 48 V 100 Ah batteries in parallel give 9.6 kWh installed. The same bank built from 12 V batteries would need strings of four.
Inverter continuous rating (W) = largest simultaneous load × (1 + headroom). Surge (W) = the other running loads + the largest motor × its starting multiple, the moment a well pump kicks in while the house is busy. With the defaults: 1,500 × 1.25 = 1,875 W continuous, and 750 + 750 × 3 = 3,000 W surge.
Battery current (A) = continuous rating ÷ (system voltage × inverter efficiency). It tells you whether the bank, its fuse and its cables can supply the inverter: 1,875 ÷ (48 × 0.9) ≈ 43 A. The same inverter on a 12 V bank would draw about 174 A, which is why larger homes move to 48 V.
Array to recover (W) = (daily energy + energy drawn during the autonomy days ÷ days to refill) ÷ (peak sun hours × delivery factor). With the defaults the bank gives up 6,667 Wh over two cloudy days; replacing that over three sunny days while still running the house takes (3,000 + 2,222) ÷ (3 × 0.75) ≈ 2,321 W, compared with 1,333 W merely to keep up with daily use.
Choices that change the answer most
Days of autonomy
Storage grows in direct proportion to the days you ask the bank to cover. Two days is a common starting point where a generator is available; homes without one, or in places with long winter storms, often plan more. Each extra day costs another full day of usable storage, so compare it with the cost of a backup generator before you commit. Our peak sun hours by state article shows how dark the hardest month gets in each state.
Chemistry and usable share
The calculator’s planning defaults are 80% usable for lithium iron phosphate and 50% for lead-acid, because many lead-acid designs use only about half the rating to protect cycle life. Your battery’s datasheet governs: it gives the recommended depth of discharge, the cycle life at that depth and the maximum charge and discharge currents. Most lithium iron phosphate batteries must not be charged below freezing unless they have built-in heating, which matters for an unheated shed or cabin.
Temperature
Batteries deliver less of their capacity when cold. If the bank will sit in an unheated space, lower the cold-weather capacity using the manufacturer’s temperature chart, or plan an insulated, ventilated enclosure that the designer and local electrical rules accept.
Recovery after bad weather
An array sized only for daily use never catches up after a storm; the bank stays partly empty until the season improves. The recovery figure above shows how much more panel capacity it takes to refill the bank in a few days. A generator, a smaller daily load during recovery or a longer refill period are the usual alternatives.
What this calculator leaves out
- Charge controller sizing. Controllers are rated by array voltage and charging current; the designer matches them to the panels and battery.
- Discharge limits and fusing. Check each battery’s continuous and peak current ratings against the inverter current above, and size fuses and cables to the manufacturer’s instructions.
- Ageing. Every battery loses capacity over its life. Many designers add a margin so the bank still covers the home in later years.
- Codes and approvals. Battery systems in homes are subject to electrical and fire codes, and most states require an electrical permit and inspection. Start with the authorities listed in your state guide.
Questions readers ask
How many batteries do I need to go off grid?
Start from energy, not from a battery count. Multiply the home’s daily watt-hours by the days the bank must carry the house without sun, then divide by the share of capacity you plan to use and by inverter efficiency. A home using 3 kWh a day with two days of autonomy, an 80% usable lithium bank and a 90% efficient inverter needs about 8.3 kWh of nominal storage, which is two 48 V 100 Ah batteries in parallel, or eight 12 V 100 Ah batteries wired as two strings of four.
How many batteries do I need for a 3000 watt inverter?
The inverter rating sets how much power the bank must deliver at once, not how long it lasts. At full output a 3,000 W inverter that is 90% efficient draws about 69 amps from a 48 V bank, 139 amps from 24 V and 278 amps from 12 V. Choose enough batteries in parallel that their combined continuous discharge rating covers that current, then check that the bank also holds enough energy for your daily use and autonomy days.
How long will a battery bank last off grid?
Divide the usable energy by the daily load. A 10 kWh lithium bank used to 80%, through a 90% efficient inverter, delivers about 7.2 kWh, or a little over two days for a home using 3 kWh a day. Cold weather, ageing and higher loads shorten that figure, so a monitor that records real use is the best check.
Should an off-grid battery bank be 12, 24 or 48 volts?
Higher voltage moves the same power with less current, which means smaller cables, lower losses and less heat. Small cabins and vans often run at 12 V, while whole-house systems usually run at 48 V. Match the bank to the inverter and charge controller you intend to use, and let the designer confirm the choice.
Is lithium or lead-acid better for an off-grid home?
Lithium iron phosphate batteries let you use more of their rated capacity, need no watering and usually last more cycles, but cost more up front and most must not be charged below freezing unless they are heated. Lead-acid is cheaper per nominal kilowatt-hour but is usually planned at about half its rating to protect its life. Compare the cost per usable kilowatt-hour over the expected life, using each manufacturer’s datasheet.
Related planning tools
- Off-grid solar calculator — build the load list that feeds this page.
- Peak sun hours by state — the winter figure for each state, from 25 years of NASA data.
- Off-grid solar planning guide — how to compare designers’ quotes on the same assumptions.
Peak sun hours come from NASA POWER 2001–2025 averages for a panel tilted at latitude at each state’s 2020 center of population, not for your parcel.